CO 4 MVI 9501/SK-FFS-R-CS

Diagram
Dimensions mm
H1 262
H2 1697
H3 122
L1 1940
L2 2000
L6 760
P1 2493
P3 650
P5 1700
P7 521
P12 529
Fire-extinguishing system installation
CO 4 MVI 9501/SK-FFS-R-CS

Estimated parameters
Pumped fluid water 100%
Fluid temperature 20 °C
Density 998.3 kg/m3
Kinematic viscosity 1 mm2/s
Product data
Control SK-FFS/4-11(24A)
Number of working pumps 3
Limit switches yes
Max. inlet pressure, Bar 10
Max. operating pressure, Bar 16
Fluid temperature 5…50 °C
Max. ambient temperature 40 °C
Protection class system IP54
Protection class of switchgear IP54
Diaphragm pressure vessel no
Dry run protection no
Motordata per Motor/Pump
Motor efficiency level IE3
Mains connection 3~380/50 Hz
Permitted voltage tolerance ± 10 %
Rated speed 2926
Rated power P2 11 kW
Rated current 20.94 А
Insulation class F
Motor protection no
Fitting dimensions
Pipe connection on the suction side DN 250
Pipe connection on the pressure side DN 200
Nominal pressure 16
Materials
Pump housing EN-GJL-250
Impeller 1.4307 [AISI304L]
Shaft 1.4057 [AISI431]
Pipework material СТ20 c КТФ
Gasket material EPDM
Ordering data
Weight approx. 1441 kg
Item number 2462001