CO 4 BL 80/150-1.5/4/SK-FFS-R-CS

Diagram
Dimensions mm
H0 1863
H1 410
H2 1006
L1 2140
L6 760
L7 2186
P0 1669
P5 1367
Fire-extinguishing system installation
CO 4 BL 80/150-1.5/4/SK-FFS-R-CS

Estimated parameters
Pumped fluid water 100%
Fluid temperature 20 °C
Density 998.3 kg/m3
Kinematic viscosity 1 mm2/s
Product data
Control SK-FFS/4-1,5(4A)/J-2,5A
Number of working pumps 3
Limit switches yes
Max. inlet pressure, Bar 10
Max. operating pressure, Bar 16
Fluid temperature 5…50 °C
Max. ambient temperature 40 °C
Protection class system IP54
Protection class of switchgear IP54
Diaphragm pressure vessel no
Dry run protection no
Motordata per Motor/Pump
Motor efficiency level IE2
Mains connection 3~400/50 Hz
Permitted voltage tolerance ± 10 %
Rated speed 1450
Rated power P2 1.5 kW
Rated current 3.4 А
Insulation class F
Motor protection no
Fitting dimensions
Pipe connection on the suction side DN 200
Pipe connection on the pressure side DN 200
Nominal pressure 16
Materials
Pump housing EN-GJL-250
Impeller EN-GJL-200
Shaft 1.4122
Pipework material СТ20 c КТФ
Gasket material
Ordering data
Weight approx. 1050 kg
Item number 2454814