CO 4 BL 80/145-11/2/SK-FFS-R-CS

Diagram
Dimensions mm
H0 1980
H1 533.2
H2 1129.2
L1 2132
L6 760
L7 2186
P0 2007
P5 1539
Fire-extinguishing system installation
CO 4 BL 80/145-11/2/SK-FFS-R-CS

Estimated parameters
Pumped fluid water 100%
Fluid temperature 20 °C
Density 998.3 kg/m3
Kinematic viscosity 1 mm2/s
Product data
Control SK-FFS/4-11(24A)/J-6,3A
Number of working pumps 3
Limit switches yes
Max. inlet pressure, Bar 10
Max. operating pressure, Bar 16
Fluid temperature 5…50 °C
Max. ambient temperature 40 °C
Protection class system IP54
Protection class of switchgear IP54
Diaphragm pressure vessel no
Dry run protection no
Motordata per Motor/Pump
Motor efficiency level IE2
Mains connection 3~400/50 Hz
Permitted voltage tolerance ± 10 %
Rated speed 2900
Rated power P2 11 kW
Rated current 22 А
Insulation class F
Motor protection no
Fitting dimensions
Pipe connection on the suction side DN 300
Pipe connection on the pressure side DN 250
Nominal pressure 16
Materials
Pump housing EN-GJL-250
Impeller EN-GJL-200
Shaft 1.4122
Pipework material СТ20 c КТФ
Gasket material
Ordering data
Weight approx. 1766 kg
Item number 2454813