CO 3 MVI 9505/SK-FFS-PN25-R

Diagram
Dimensions mm
H1 262
H2 1824
H3 130
L1 1444
L2 1500
L6 1200
P1 2248
P3 630
P5 1620
P7 383
P12 607
Fire-extinguishing system installation
CO 3 MVI 9505/SK-FFS-PN25-R

Estimated parameters
Pumped fluid water 100%
Fluid temperature 20 °C
Density 998.3 kg/m3
Kinematic viscosity 1 mm2/s
Product data
Control SK-FFS/3-55(95A)/V-3~1,0A
Number of working pumps 2
Limit switches yes
Max. inlet pressure, Bar 16
Max. operating pressure, Bar 25
Fluid temperature 5…50 °C
Max. ambient temperature 40 °C
Protection class system IP54
Protection class of switchgear IP54
Diaphragm pressure vessel no
Dry run protection no
Motordata per Motor/Pump
Motor efficiency level IE2
Mains connection 3~380/50 Hz
Permitted voltage tolerance ± 10 %
Rated speed 2965
Rated power P2 45 kW
Rated current 80.8 А
Insulation class F
Motor protection no
Fitting dimensions
Pipe connection on the suction side DN 200
Pipe connection on the pressure side DN 150
Nominal pressure 25
Materials
Pump housing EN-GJL-357
Impeller 1.4307 [AISI304L]
Shaft 1.4057 [AISI431]
Pipework material 1.4307 [AISI304L]
Gasket material EPDM
Ordering data
Weight approx. 1540 kg
Item number 2462494