CO 3 IPN 80/170-11,0/2/SK-FFS-R-CS

Diagram
Dimensions mm
H0 1358
H1 445
H2 1915
H3 1133
L1 2055
L2 2100
L6 600
P1 1880
P2 1150
P3 1470
P4 233
P5 1318
P7 1353
Fire-extinguishing system installation
CO 3 IPN 80/170-11,0/2/SK-FFS-R-CS

Estimated parameters
Pumped fluid water 100%
Fluid temperature 20 °C
Density 998.3 kg/m3
Kinematic viscosity 1 mm2/s
Product data
Control SK-FFS/3-11(24A)/V-3~10A
Number of working pumps 2
Limit switches yes
Max. inlet pressure, Bar 16
Max. operating pressure, Bar 16
Fluid temperature 5…50 °C
Max. ambient temperature 40 °C
Protection class system IP54
Protection class of switchgear IP54
Diaphragm pressure vessel no
Dry run protection no
Motordata per Motor/Pump
Motor efficiency level IE2
Mains connection 3~380/50 Hz
Permitted voltage tolerance ± 10 %
Rated speed 2900
Rated power P2 11 kW
Rated current 21 А
Insulation class F
Motor protection no
Fitting dimensions
Pipe connection on the suction side DN 200
Pipe connection on the pressure side DN 100
Nominal pressure 16
Materials
Pump housing EN-GJL-200
Impeller EN-GJL-200
Shaft AISI 304
Pipework material СТ20 c КТФ
Gasket material EPDM
Ordering data
Weight approx. 1300 kg
Item number 2468967