CO 3 IPN 150/390-45,0/4/SK-FFS-R-CS

Diagram
Dimensions mm
H0 1665
H1 580
H3 1397
L1 2032
L2 2100
L6 1000
P1 2582
P2 1500
P3 1952
P4 285
P5 1825
P7 1860
Fire-extinguishing system installation
CO 3 IPN 150/390-45,0/4/SK-FFS-R-CS

Estimated parameters
Pumped fluid water 100%
Fluid temperature 20 °C
Density 998.3 kg/m3
Kinematic viscosity 1 mm2/s
Product data
Control SK-FFS/3-55(95A)/V-3~10A
Number of working pumps 2
Limit switches yes
Max. inlet pressure, Bar 16
Max. operating pressure, Bar 16
Fluid temperature 5…50 °C
Max. ambient temperature 40 °C
Protection class system IP54
Protection class of switchgear IP54
Diaphragm pressure vessel no
Dry run protection no
Motordata per Motor/Pump
Motor efficiency level IE2
Mains connection 3~380/50 Hz
Permitted voltage tolerance ± 10 %
Rated speed 1450
Rated power P2 45 kW
Rated current 85.4 А
Insulation class F
Motor protection no
Fitting dimensions
Pipe connection on the suction side DN 250
Pipe connection on the pressure side DN 150
Nominal pressure 16
Materials
Pump housing EN-GJL-200
Impeller EN-GJL-200
Shaft AISI 304
Pipework material СТ20 c КТФ
Gasket material EPDM
Ordering data
Weight approx. 2750 kg
Item number 2468995