CO 3 BL 80/165-22/2/SK-FFS-R

Diagram
Dimensions mm
H0 1907
H1 452
H2 1078
L1 1590
L6 760
L7 1636
P0 1932
P5 1489
Fire-extinguishing system installation
CO 3 BL 80/165-22/2/SK-FFS-R

Estimated parameters
Pumped fluid water 100%
Fluid temperature 20 °C
Density 998.3 kg/m3
Kinematic viscosity 1 mm2/s
Product data
Control SK-FFS/3-22(50A)/J-10A
Number of working pumps 2
Limit switches yes
Max. inlet pressure, Bar 10
Max. operating pressure, Bar 16
Fluid temperature 2…40 °C
Max. ambient temperature 40 °C
Protection class system IP54
Protection class of switchgear IP54
Diaphragm pressure vessel no
Dry run protection no
Motordata per Motor/Pump
Motor efficiency level IE2
Mains connection 3~400/50 Hz
Permitted voltage tolerance ± 10 %
Rated speed 2900
Rated power P2 22 kW
Rated current 40.7 А
Insulation class F
Motor protection no
Fitting dimensions
Pipe connection on the suction side DN 250
Pipe connection on the pressure side DN 200
Nominal pressure 16
Materials
Pump housing EN-GJL-250
Impeller EN-GJL-200
Shaft 1.4122
Pipework material 1.4571 [AISI316Ti ]
Gasket material
Ordering data
Weight approx. 1246.5 kg
Item number 2453909