CO 3 BL 50/130-5.5/2/SK-FFS-R-CS
Diagram
|
Dimensions |
mm |
H0 |
1863 |
H1 |
356.4 |
H2 |
790.4 |
L1 |
1594 |
L6 |
600 |
L7 |
1594 |
P0 |
1546 |
P5 |
1278 |
|
|
Fire-extinguishing system installation |
CO 3 BL 50/130-5.5/2/SK-FFS-R-CS |
|
|
|
Kinematic viscosity |
1 mm2/s |
|
Control |
SK-FFS/3-5,5(12A)/J-6,3A |
|
Number of working pumps |
2 |
|
|
Max. inlet pressure, Bar |
10 |
|
Max. operating pressure, Bar |
16 |
|
Fluid temperature |
5…50 °C |
|
Max. ambient temperature |
40 °C |
|
Protection class system |
IP54 |
|
Protection class of switchgear |
IP54 |
|
Diaphragm pressure vessel |
no |
|
|
Motor efficiency level |
IE2 |
|
Mains connection |
3~400/50 Hz |
|
Permitted voltage tolerance |
± 10 % |
|
|
|
|
|
|
Pipe connection on the suction side |
DN 150 |
|
Pipe connection on the pressure side |
DN 125 |
|
|
|
|
|
Pipework material |
СТ20 c КТФ |
|
|
|
|
|