CO 2 MVI 7001/1/SK-FFS-R

Diagram
Dimensions mm
H1 262
H2 1697
H3 122
L1 940
L2 1000
L6 600
P1 2350
P3 650
P5 1650
P7 471
P12 529
Fire-extinguishing system installation
CO 2 MVI 7001/1/SK-FFS-R

Estimated parameters
Pumped fluid water 100%
Fluid temperature 20 °C
Density 998.3 kg/m3
Kinematic viscosity 1 mm2/s
Product data
Control SK-FFS/2-4,0(10A)/J-4,0A/V-3~1,0A
Number of working pumps 1
Limit switches yes
Max. inlet pressure, Bar 10
Max. operating pressure, Bar 16
Fluid temperature 2…40 °C
Max. ambient temperature 40 °C
Protection class system IP54
Protection class of switchgear IP54
Diaphragm pressure vessel no
Dry run protection no
Motordata per Motor/Pump
Motor efficiency level IE2
Mains connection 3~400/50 Hz
Permitted voltage tolerance ± 10 %
Rated speed 2900
Rated power P2 4 kW
Rated current 7.8 А
Insulation class F
Motor protection no
Fitting dimensions
Pipe connection on the suction side DN 200
Pipe connection on the pressure side DN 200
Nominal pressure 16
Materials
Pump housing EN-GJL-250
Impeller 1.4307 [AISI304L]
Shaft 1.4057 [AISI431]
Pipework material 1.4571 [AISI316Ti ]
Gasket material EPDM
Ordering data
Weight approx. 616 kg
Item number 2453593