CO 2 IPN 80/155-7,5/2/SK-FFS-R-CS

Diagram
Dimensions mm
H0 1266
H1 427
H2 1915
H3 1065
L1 1344
L2 1400
L6 600
P1 1754
P2 1150
P3 1470
P4 263
P5 1239
P7 1274
Fire-extinguishing system installation
CO 2 IPN 80/155-7,5/2/SK-FFS-R-CS

Estimated parameters
Pumped fluid water 100%
Fluid temperature 20 °C
Density 998.3 kg/m3
Kinematic viscosity 1 mm2/s
Product data
Control SK-FFS/2-7,5(18A)/J-6,3A/V-3~10A
Number of working pumps 1
Limit switches yes
Max. inlet pressure, Bar 16
Max. operating pressure, Bar 16
Fluid temperature 5…50 °C
Max. ambient temperature 40 °C
Protection class system IP54
Protection class of switchgear IP54
Diaphragm pressure vessel no
Dry run protection no
Motordata per Motor/Pump
Motor efficiency level IE2
Mains connection 3~380/50 Hz
Permitted voltage tolerance ± 10 %
Rated speed 2900
Rated power P2 7.5 kW
Rated current 14.5 А
Insulation class F
Motor protection no
Fitting dimensions
Pipe connection on the suction side DN 125
Pipe connection on the pressure side DN 80
Nominal pressure 16
Materials
Pump housing EN-GJL-200
Impeller EN-GJL-200
Shaft AISI 304
Pipework material СТ20 c КТФ
Gasket material EPDM
Ordering data
Weight approx. 630 kg
Item number 2468922