CO 2 Helix V 3605/2/SK-FFS-R-CS

Diagram
Dimensions mm
H1 225
H2 1695
H3 120
L1 948
L2 1080
L6 600
P1 1804
P3 500
P5 1354
P7 406
P12 448
Fire-extinguishing system installation
CO 2 Helix V 3605/2/SK-FFS-R-CS

Estimated parameters
Pumped fluid water 100%
Fluid temperature 20 °C
Density 998.3 kg/m3
Kinematic viscosity 1 mm2/s
Product data
Control SK-FFS/2-15(32A)/J-6,3A/V-3~1,0A
Number of working pumps 1
Limit switches yes
Max. inlet pressure, Bar 10
Max. operating pressure, Bar 16
Fluid temperature 5…50 °C
Max. ambient temperature 40 °C
Protection class system IP54
Protection class of switchgear IP54
Diaphragm pressure vessel no
Dry run protection no
Motordata per Motor/Pump
Motor efficiency level IE2
Mains connection 3~400/50 Hz
Permitted voltage tolerance ± 10 %
Rated speed 2935
Rated power P2 15 kW
Rated current 25.2 А
Insulation class F
Motor protection no
Fitting dimensions
Pipe connection on the suction side DN 100
Pipe connection on the pressure side DN 100
Nominal pressure 16
Materials
Pump housing EN-GJL-250
Impeller 1.4307 [AISI304L]
Shaft 1.4057 [AISI431]
Pipework material СТ20 c КТФ
Gasket material EPDM
Ordering data
Weight approx. 586 kg
Item number 2454843