CO 2 BL 125/265-15/4/SK-FFS-R-CS

Diagram
Dimensions mm
H0 1894
H1 448
H2 1071
L1 1332
L6 600
L7 1380
P0 2102
P5 1660
Fire-extinguishing system installation
CO 2 BL 125/265-15/4/SK-FFS-R-CS

Estimated parameters
Pumped fluid water 100%
Fluid temperature 20 °C
Density 998.3 kg/m3
Kinematic viscosity 1 mm2/s
Product data
Control SK-FFS/2-15(32A)/J-6,3A/V-3~10A
Number of working pumps 1
Limit switches yes
Max. inlet pressure, Bar 10
Max. operating pressure, Bar 16
Fluid temperature 5…50 °C
Max. ambient temperature 40 °C
Protection class system IP54
Protection class of switchgear IP54
Diaphragm pressure vessel no
Dry run protection no
Motordata per Motor/Pump
Motor efficiency level IE2
Mains connection 3~400/50 Hz
Permitted voltage tolerance ± 10 %
Rated speed 1450
Rated power P2 15 kW
Rated current 29.8 А
Insulation class F
Motor protection no
Fitting dimensions
Pipe connection on the suction side DN 250
Pipe connection on the pressure side DN 250
Nominal pressure 16
Materials
Pump housing EN-GJL-250
Impeller EN-GJL-200
Shaft 1.4122
Pipework material СТ20 c КТФ
Gasket material
Ordering data
Weight approx. 1125.4 kg
Item number 2454496